Compliance Requirements
The Ontario Fire Code regulates fire prevention and life safety requirements. The particular requirement for Fire Prevention, Fire Detection, and Life Safety depends upon how a property is occupied. A minimum level of fire protection will increase due to the existence of hazards and when properties have an increased number of occupants.
The minimum fire protection and life safety requirements for the Licensed Premises listed in By-Law Number 2021-065 are as follows;
Smoke Alarm(s)
Smoke Alarm(s) shall be installed:
- When a bedroom in a Licensed Premises is served by a hallway, in the hallway,
- When a bedroom in a Licensed Premises is not served by a hallway, between the sleeping area and the remainder of the Licensed Premises,
- When a bedroom is not within a Licensed Premises, in the bedroom, and
- On each storey without a bedroom in a Licensed Premises.
Note: Replacement of hard-wired smoke alarms with battery operated devices is not permitted.
When are CO Alarm(s) required?
Carbon Monoxide Alarm(s) shall be installed in every building that contains a residential occupancy and:
- a fuel-burning appliance,
- a fireplace, or
- a storage garage (attached garage)
Where to install CO Alarm(s)
- When a fuel-burning appliance or a fireplace is installed in a Licensed Premises, a CO alarm shall be installed adjacent to each bedroom.
- When a Licensed Premises has a storage garage attached to it, a CO alarm shall be installed adjacent to each bedroom that has a common wall or common floor/ceiling assembly with the storage garage.
- A CO alarm shall be mechanically fixed, attached, plugged in or placed at the manufacturer’s recommended height or, if the manufacturer has not recommended a height, on or near the ceiling.
- A CO alarm that is installed adjacent to a bedroom shall be equipped with an alarm that is audible throughout the bedroom, even if any door(s) between the carbon monoxide alarm and any bedroom is/are closed.
Fire Safety Plan
All residential properties that have an occupant load that exceeds 10 must submit a Fire Safety Plan to the Selwyn Fire Department for approval prior to an inspection. Templates for the Fire Safety Plan are available from the Selwyn Fire Department by calling (705) 292-7282.
Lodging Houses
A Small or Large Lodging House requires an inspection from the Selwyn Fire Department. Please contact 705-292-7282 to arrange a licensing inspection of the property.